Permit: T03CM04982

Parcel: 131070650

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T03CM04982

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 11 PSI TEST FROM METER TO BOILER ONLY AT MECHANICAL BLDG OK
2) PLEASE SUPPLY BOILER INSTALLATION INSTRUCTIONS FOR VENT TERMINATION. COMPLETE THIS WORK FOR GAS CARD
07/29/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) SHALL PROVIDE MINIMUM 10 PSI TEST FOR 15 MINUTES WITH NO PRESSURE DROP. WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLEAS AND COUPLINGS SHALL BE USED