Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T03CM04982
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 11 PSI TEST FROM METER TO BOILER ONLY AT MECHANICAL BLDG OK 2) PLEASE SUPPLY BOILER INSTALLATION INSTRUCTIONS FOR VENT TERMINATION. COMPLETE THIS WORK FOR GAS CARD |
|
07/29/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) SHALL PROVIDE MINIMUM 10 PSI TEST FOR 15 MINUTES WITH NO PRESSURE DROP. WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLEAS AND COUPLINGS SHALL BE USED |