Permit: T03CM04982

Parcel: 131070650

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T03CM04982

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2005 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
03/15/2005 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :* (2) 8" RAIN DRAIN & OVERFLOW RAIN DRAINS ON EAST SIDE OF BUILDING 5 PSI AIR TEST FROM PARKING DECK TO WALL PENETRATION FOR OVERFLOW, AND TO ADDED BUBBLER BOXES PER RED LINE DRAWING ON SITE. PARTIAL PENDING CITY APPROVAL OF RED LINE ON SITE.
03/10/2005 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :* AIR OR WATER TEST REQUIRED WITH RED LINE DRAWING ON SITE OF ( 2) 8" RAIN DRAINS TO ( 2) BUBBLER BOXES WITH CITY APPROVED PLAN TO FOLLOW.
02/14/2005 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :* PARTIAL APPROVAL 6" OFRD INTO 8" SCH40 SOUTH COUNTER WATER TEST OK
02/09/2005 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :* 6" RD & 6" OFRD TO 8'' PVC SCH40 PIPING AT NORTH EAST WATER TEST OK. 6''RD & 6"OFRD TO 8" PVC SCH40 PIPING AT SOUTH EAST WATER TEST ( PARTIAL APP) 1) NEED TO HAVE APPROVED MATERIAL UNDERGROUND INSIDE BUILDING. INSTALL FOR APPROVED PLAN. 6'' RD & 6" OFRD TO 8" PVC SCH 40 PIPING AT CENTER NORTH WATER TEST OK.6'' RD TO 8'' PVC SCH 40 PIPING AT SOUTH CENTER 5 PSI AIR TEST OK 6"RD & 6" OFRD TO 8'' PVC SCH 40 PIPING AT SOUT WEST 5 PSI AIR TEST OK. 2) PROVIDE LETTER FROM ENGINEER WITH HIS STAMP OK FOR PVC SCH 40 IN PLACE OF SPEC IRON PIPING.