Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04982
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE LETTER ALL GEAR, BUS AND TERMINATIONS HAVE BEEN TORQUED PER MANUFACTURER 2) NEED TO SEE A.I.C. RATING OF GEAR AND WHAT THE AVAILABLE FAULT CURRENT IS AT THE GEAR 3) SCREW OR CLIP FIXTURES TO GRID BOXES OVERFILLED |
|
02/01/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL MOVE LA-2 AS DISCUSSED TRANSF. LOCATION IS OK AS IS PARTIAL. PAST COUNTER SOFFIT OK ROOM 116. | |
01/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 133, 136, 134, 135,113, 114, 123, 124, 115, 119, 115, 175, PARTS STORAGE SHOWROOM -100 LIDS @ SW CORNER ROOMS 152, 156, 160, 161, 162, 163, ENT. 160-161. ??? 115-119 | |
01/11/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ROOMS 104 THRU 113, ROOM 100 THRU 103, ROOM 125 THRU 132, ROOMS 136 THRU 148, ROOM 175-ALL OK TO COVER |