Permit: T03CM04982

Parcel: 131070650

Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T03CM04982

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2005 STEM WALL/RETAINING WALL Approved IVRS - Inspection :*
01/13/2005 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :* 1025 EXTERIOR SHEATING HIGH SOFFITS OK SHEATING OK CDS OK SOUTH SIDE LOW WALLS UNDER DRIVE PARTIAL
07/08/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
06/08/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :* 1) COLS G10 & H10 OK TO CLOSE AFTER SPEC INSP ON WELD PLATES & WELDABLE REBAR PER SK2. 2) F9 & F10 OK TO CLOSE
06/04/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :* COLS IN MEZZ AREA 10' 6"-20' OK AS NOTED
06/03/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :* 1) TOP OF COLS LINE8/B, C, D, E. 2) TOP OF COLS LINE 9, D. 3) COLUMN @ ELEVATOR SHAFT OK
06/02/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
06/01/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*COLS LINE J/11-14 LINE K/11-14
05/27/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) COLS LINE J CC5 COLS AT 11,12, 13, 14 OK 2) CC7 COL AT 10/E OK
05/26/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*
05/25/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) LINE 8 TO 10'-6" B-H 2) LINE 9 TO 10'-6" E-H 3) LINE 10/E-H MATCH VBERTS TO DOWELS FOR PROPER CLEARANCE 4) LINE 12-B,C,D AND E OK 5) LINE 13-CDEF OK 6) LINE 14-BCDE ADD SPACERS/CHAIRS OK TO CLOSE
05/24/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) LINE 8 TO 10'-6" COLS. OK TO CLOSE AND POUR
05/21/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) COLUMNS LINE 11 OK 2) 3 COLUMNS LINE 13 OK TO CLOSE WHEN SPEC. INSPECTOR CONFIRMS FINAL TIES
05/20/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) COLUMNS LINE 5, LINE 6-OK
05/18/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) LINE 5 COLS. A) TIE ADJACENT DOWEL/COL VERTS TOGETHER B) RING TIES TO BE HORIZONTAL-PLEASE CLEAN UP DISTURBED TIES
05/17/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) LINE 2/BCD 2) LINE 3/ALL
05/13/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :*/ 1) LINE B AND C OF TO POUR 2) LINE 2 E,F AND G OK TO POUR 3) LINE 4 OK TO CLOSE 4) LINE 7 OK TO CLOSE
05/12/2004 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection :* 1) OPEN FORMS FOR INSP AT COLUMNS. 2) RFI ENG ABOUT RANDOM VERTICAL DOWELS UP TO 5" SHORT (72" REQ)
"IT IS NECESSARY THAT C.O.T. PERFORM ALL INSP. SPEC INSP IS IN ADDITION TO C.O.T."
COLUMNS: LINE 1 B DENIED EXPOXIED DOWEL OUT OF CAGE. C- OK TO CLOSE & POUR. D- DENIED DOWEL OUT OF CAGE.
LINE 2 E, F, G- YOU NEED TO PROVIDE 1 1/2" CLEAR TO TIES. OK TO CLOSE I NEED TO REINSP CLEARANCES BEFORE YOU POUR.