Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM04981
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* APPROVED. OK FOR FINAL C OF O | |
| 09/15/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)CONDENSATE MUST BE 3/4" I.D. PROVIDE ROOF JACKS ON DRAIN LINE 2)PROVIDE SCREENS ON T-TOPS 3)SUPPORT OR SECURE ELEC. DISCONNECTS. CONDUIT NOT CONNECTED PROPERLY. DO NOT USE WHITE WIRE FOR HIGH VOLTAGE 4)PROVIDE A BLOCK & CLAMP UNDER GAS PIPE. 5)TERMINATE CONDENSATE 6" ABOVE GROUND RECALL FOR INSPECTION |