Permit: T03CM04981

Parcel: 131080060


Addresses:

5952 E 22ND ST #01


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM04981

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ WTR TEST ON TUB AND STOOL AND CONNECTION OK.
05/26/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ WTR TEST ON NEW WASTE AND VENT AS PER APPROVED PLAN FOR UNDERGROUND ONLY OK. PROVIDE AIR OR WTR TEST ON EXTERIOR HCS CONNECTION WITH TUB AND STOOL ON EXISTING.
05/21/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/19/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 10' HEAD IS REQUIRED ON WASTE AND VENT TEST. 2) HAVE YOUR PLAN CHANGED AND CITY APPROVED TO REFLECT ACTUAL EXISTING SITUATION AND ADDITIONAL WORK IN EXISTING BATHROOM SHOWN AS JUST NEW FIXTURES. 3)EXPOSE ALL WORK AND TEST ALL WORK IN EXISTING RESTROOM. CAP ALL DEMO PLBG BELOW SLAB WITH APPROVED CAP. 4) HAVE YOUR PBG CONTRACTOR ON SITE AT TIME OF NEXT INSP. 5) REMOVE BACKWTR VALVE OR HAVE IT ADDED TO YOUR CITY APPROVED PLAN IF REQUIRED.
05/12/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ INSTALL PER PLAN WITH APPROVED DRAINAGE FITTINGS.