Inspection History: SHEET ROCK NAILING

Permit Number - T03CM04981

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2004 SHEET ROCK NAILING Approved IVRS - Inspection :*
07/28/2004 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*/ 1) TAPE ALL BUT BATHROOM EAST UNIT
07/27/2004 SHEET ROCK NAILING Denied IVRS - Inspection :
i NEED LISTINGS FOR PLASTIC ELEC BOXES WITH INFORMATION ABOUT HOW CLOSE THEY MAY BE IN A 1 HR FIRE BARRIER
YOU MAY USE PLASTIC REFRIG WATER SUPPLY BOXES IN A FIRE BARRIER
ALL PENETRATIONS IN FIRE BARRIER MUST BE SEALED IN ACCORDANCE WITH A LISTED FIRE STOP SYSTEM - THIS INCLUDES ABOVE CEILING
ATTIC ACCESS REQUIRED
NAIL OF CEILING IN ALL CLOSETS
STUCCO LATH REQUIRES PROPER FLUSHING WHERE FOAM IS CUT