Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/1)CORRECTIONS MADE OK. 2)OK TO COVER ALL AREAS 3)CLOSET FLANGES OK | |
| 09/20/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL USE APPROVED STRAPS ON ALL HORIZONTAL VENTING EVERY 4'-0" 2) SHALL PROVIDE SHUT OFF VALVE AND UNION TRAP PRIMER 3) SHALL USE DBL FIXTURE FITTING FOR LAVATORY TRAP ARMS 4) SOIL WATER TEST IS OK FOR 2-3" RWL FRONT AND REAR |
|
| 09/20/2004 | PLUMBING - INTERMEDIATE | Denied | 1) ONE MORE TIME-CHANGE OF DIRECTION, CHANGE OF ELEVATION AND END OF BRANCHES 2) NEED TO SEE CLOSET FLANGES 3) TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEGREE WITH CLEAN OUT REQUIRED DRAINAGE FITTINGS 4) HORIZONTAL X HORIZONTAL CHANGE TO BE A SWEEP 5) REVIEW TABLE 3-1 | |
| 09/14/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/STILL UNABLE TO LOCATE ROOF DRAINS. NO CHANGE FROM LAST INSPECTION. THERE ARE OTHER CODE VIOLATIONS. SEE TABLE 3-1 AND REMEMBER CHANGE OF DIRECTION, CHANGE OF ELEVATION, END OF BRANCHES |
|
| 09/13/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/1)CAREFULLY REVIEW 712.294 UPC-TESTING 2)REVIEW 1002.2 TRAP ARMS 3)NOTE HANGER S AND SUPPORTS ARE REQUIRED AT EACH CHANGE OF DIRECTION, EACH CHANGE OF ELEVATION, AT THE END OF BRANCHES AND THEN EVERY SO MANY FEET AS REQUIRED IN TABLE 3-1 GAWPC? |