Permit: T03CM04970

Parcel: 11611005H

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM04970

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/1)CORRECTIONS MADE OK. 2)OK TO COVER ALL AREAS 3)CLOSET FLANGES OK
09/20/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHALL USE APPROVED STRAPS ON ALL HORIZONTAL VENTING EVERY 4'-0" 2) SHALL PROVIDE SHUT OFF VALVE AND UNION TRAP PRIMER 3) SHALL USE DBL FIXTURE FITTING FOR LAVATORY TRAP ARMS 4) SOIL WATER TEST IS OK FOR 2-3" RWL FRONT AND REAR
09/20/2004 PLUMBING - INTERMEDIATE Denied 1) ONE MORE TIME-CHANGE OF DIRECTION, CHANGE OF ELEVATION AND END OF BRANCHES 2) NEED TO SEE CLOSET FLANGES 3) TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEGREE WITH CLEAN OUT REQUIRED DRAINAGE FITTINGS 4) HORIZONTAL X HORIZONTAL CHANGE TO BE A SWEEP 5) REVIEW TABLE 3-1
09/14/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/STILL UNABLE TO LOCATE ROOF DRAINS. NO CHANGE FROM LAST INSPECTION. THERE ARE OTHER CODE VIOLATIONS.
SEE TABLE 3-1 AND REMEMBER CHANGE OF DIRECTION, CHANGE OF ELEVATION, END OF BRANCHES
09/13/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)CAREFULLY REVIEW 712.294 UPC-TESTING 2)REVIEW 1002.2 TRAP ARMS 3)NOTE HANGER S AND SUPPORTS ARE REQUIRED AT EACH CHANGE OF DIRECTION, EACH CHANGE OF ELEVATION, AT THE END OF BRANCHES AND THEN EVERY SO MANY FEET AS REQUIRED IN TABLE 3-1 GAWPC?