Permit: T03CM04970

Parcel: 11611005H

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T03CM04970

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/07/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
WALKWAY & POOL LANDSCAPE LIGHTING.
11/05/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ 1) 2" PVC TO POOL BOX FROM SES AND 3/4 PVC FOR SITE LITES-SOUTH EAST CORNER
10/20/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The conduit is not installed per code.| 240*/1)THE POWER LINE PVC MUST BE SCHEDULE 40 PVC. THE PIPE YOU HAVE USED IS A THINWALL NON UL LISTED OR SCHEDULE RATED PRODUCT NOT CODE APPROVED FOR THE USE
05/27/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ THREE 3/0 COPPER TAILS I BELIEVE ARE TO BE FOR BLD STEEL AND GAS AND WTR ALSO A #4 COPPER TO REBAR SW CORNER.
05/19/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ UNDERSLAB PVC TO SUB PANEL.