Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/17/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 11/13/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/ 1) FINISH #1 AND 7 OF PREVIOUS INSPECTIONS |
| 11/04/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CONDUIT NOT TO BE TIED TO GRID RUNNERS 2) FILL UNUSED OPENINGS IN JUNCTION BOX 3) FINISH CONDUIT RUNS 4) PLUMBING COPPER LINES NOT TO BE SUPPORTED OFF OF CONDUIT 5) VDV CABLES NOT TO BE LAYING ON GRID TILES 6) SUPPORT FLEX CONDUIT AS PER CODE 7) RE-LOCATED LIGHTING TO HAVE SUPPORT WIRES AND ATTACHED TO GRID 8) VERIFY CONDUCTOR FILL AT BOXES |