Inspection Status: Denied

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
02/17/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0999*/ 1) NAIL SHEET ROCK THRU-OUT PER GYP STANDARDS
02/17/2004 SHEET ROCK NAILING Approved IVRS - Inspection 0000*
02/11/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0175*FOLLOW PLAN AND CODE. #1 SHEAR WALL NOT NAILED 7" O.C.; #5 SHEAR WALL CLOSET NOT NAILED
02/09/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0175*/ 1) #5 SHEAR WALL NOT NAILED AT BOTTOM AROUND FURNACE PLATFORM 2) #1 SHEAR WALL NOT NAILED AT BOTTOM AT FURANCE PLATFORM 3) #5 SHEAR WALL NOT ANILED AT TOP PLATE BY DUCTWORK 4) #5 SHEAR WALL NOT NAILED IN CLOSET 5) SHEAR GYPISUM PANELS LESS THAN 9 FEET LONG MUST BE INSTALLED VERTICALLY 6) GAPS LARGER THAN 1/4" ALLOWED 7) FILL ALL GAPS LARGER THAN 1/8" WITH HARD SETTING COMPOUND