Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM04925

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2004 MECHANICAL - INTERMEDIATE Approved
02/25/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) SUSPENDED ROUGH DUCT ONLY. NOTE: DRYER DUCT (PROJECTED) NEEDS TO BE SMOOTH WALL 4" OR OVAL CONNECTOR PIPE. NO FLEX ALLOWED EXCEPT SMALL PE. OUT OF DRYER TO CONNECT TO RIDGID VENT 2) WHERE IS 1" CU (COPPER) CONDENSATE LINE ? IN WALL ? 3) EXHAUST DUCTS LOCATED IN RETRUN AIR PLENIUMS NEED TO BE RIGID SHT. MTL PIPE WITH SEALED JOINTS. NO PORTIONS OF FLEXABLE DUCT