Permit: T03CM04925

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM04925

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/13/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
02/12/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*/ 1) J-BOXES IN SOFFITS MUST BE MOVED TO A LOCATION WHERE THEY WILL BE READILY ACCESSABLE. 2) M.C. CABLE WITHIN 1ΒΌ" OF FACE OF STUDS MUST BE NAIL PLATED. 3) MOVE RECEPTACLE COVERED BY STUD - AT RIGHT FRONT. 4) SIGN CIRCUIT AND J-BOX MISSING. CORRECT AND RE-CALL.