Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/12/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : 1) PROTECT CONDUCTORS INSIDE BOXES. 2) FINISH ITEMS # 1, 2, 3, 6, 7. |
|
| 10/11/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)SUPPORT NM? CABLES ABOVE PANEL & BELOW 2)FINISH #2 PREVIOUS 3)TIGHTEN LOOSE FITTINGS AT EXHAUST FANS & PANELS 4)PROTECT CABLES AT STUDS 5)MAINTAIN WORKING CLEARENCES FOR A/C DISCONNECTS 6)CABLE TO BE SECURED TO PANEL 7)SECURE NM CABLE WITHIN 12" OF EXHAUST FANS | |
| 10/08/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| USE ROMEX CLAMP TYPE CONNECTORS FOR BATHROOM FANS TOO MANY CABLE TERMINATION INTO ROMEX CONNECTORS AT PANEL, CHECK LISTING AND INSTALL PER MFG. ROMEX NOT TERMINATED INTO BOX FOR OUTSIDE LIGHT |