Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM04907

Parcel: 121120680

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FINAL. LAST INSPECTOR TO CLEAR
03/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) AIC RATING HAS BEEN VERIFIED TO 22,000 AIC WE HAVE 10,000 AIC MAINS. 2) FILL UNUSED OPENINGS IN BOXES. 3) COMPLETE ITEMS # ?, 10, 11, 15. RECEIVED LETTERS FOR AIC RATING, LIGHTING, AND DEVICES
03/11/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio A REFEE HAS BEEN ACCESSED PER ADMIN CODES AND PREVIOUS WRITE-UP
03/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
IF ALL ITEMS NOT COMPLETED FOR NEXT INSPECTION A REFEE WILL BE ISSUED 1) PROPERLY INSTALL IRRIGATION ELECTRIC REDUCING WASHERS AND TIGHTEN FITTINGS. 2) WE HAVE EXPOSED NM CABLES BY SERVICE. 3) BREEZWAY LIGHTS NOT AS PER PLAN. ARCH TO SUBMIT LETTER FOR APPROVAL OF LIGHTS INSTALLED. 4) WHERE IS TIME CLOCK? 5) WE STILL HAVE CLEARENCE VILOATIONS AT A/C DISCONNECTS AND LABEL DISCONNECTS. 6) GROUNDING IN GUTTERS ( A/C) NOT ALLOWED TO USE SHEET METAL SCREWS AND CLEAN SURFACES UNDER LUGS 250.8 250.12 7) HOOD RECEPTICAL NOT ACCESSABLE, NEED APPROVED CONNECTOR TO HOOD. 8) CONDUCTOR TO FULLY TERMINATE UNDER TERMINAL SCREWS AT DEVICES 9) COMPLETLY CLEAN PANEL OF BUSS SURFACES TO PREVENT FIRE HAZARD PER 110.12 10) BREAKER AMPACITY TO MATCH CONDUCTOR SIZE PER 336.26 11) LIGHT FIXTURE TO HAVE A JUNCTION BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 370-20 ( BOTH LIGHT FANS & DEVICES BOXES) FLUSH AT COMBUSTIBLES. 13) APPROVED STRAIN RELIEF CONNECTORS NEEDED FOR APPLIANCES. 14) PLEASE VERIFY AIC RA? NEEDED FOR MAINS. PLANS HAVE SERVICES AT 42KAIC AND 100KAIC. 15) WHERE ARE HAND? LOCKOUTS AS PER PLANS NOTES? (2) IDENTIFY EXACT HVAC UNITS TO PANEL BOARD NOTE (1) 16) PLANS CALL FOR 20 AMP DEVICES 17) BOND COLD WATER SIDE OF WATER PIPING 18) SUPPORT FLEX CONDUIT
02/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* 1) ARC FAULT BREAKERS REQUIRED SEE NOTE ONPLAN E-4 2) OUTDOOR WALL PACKS NOT PER PLAN 3) AC UNIT DISCONNECTS IN VIOLATION OF 110-26 NEC WORKING CLEARANCE