Permit: T03CM04904

Parcel: 11611005H

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM04904

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/25/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: BENT NAILS NOT APPROVED TO SUPPORT ROMEX-FEEDERS TO PANELS & RANGE OUTLETS, USE LISTED STAPLES FOR CABLE SUPPORT PLEASE LEAVE MSG ON NEXT INSPECTION WITH ELECTRICIAN FORMAN PH# SO INSPECTOR CAN CALL.
02/23/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) WHERE NOT SUPPORTED BY BORED HOLES IN WOOD STUDS OR CEILING JOISTS- ROMEX MUST BE SUPPORTED AT 4 1/2" INTERVALSK PER NEC. CHECK HORIZONTAL RUNS THRU FIRE WALLS, & CEILINGS THRU OUT.
08/10/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/SEE BLD. #2 WRITE UP
08/06/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) SEE BLDG #2 WRITE-UP