Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04904
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/25/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: BENT NAILS NOT APPROVED TO SUPPORT ROMEX-FEEDERS TO PANELS & RANGE OUTLETS, USE LISTED STAPLES FOR CABLE SUPPORT PLEASE LEAVE MSG ON NEXT INSPECTION WITH ELECTRICIAN FORMAN PH# SO INSPECTOR CAN CALL. |
|
| 02/23/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) WHERE NOT SUPPORTED BY BORED HOLES IN WOOD STUDS OR CEILING JOISTS- ROMEX MUST BE SUPPORTED AT 4 1/2" INTERVALSK PER NEC. CHECK HORIZONTAL RUNS THRU FIRE WALLS, & CEILINGS THRU OUT. |
|
| 08/10/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/SEE BLD. #2 WRITE UP |
|
| 08/06/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) SEE BLDG #2 WRITE-UP |