Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/08/2004 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 12/01/2004 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/1)1ST FLR. NOT ALL CONDENSATE DRAINS HAVE BEEN RUN, BLDG #4 2)2ND FLR. NORTH EAST (NE) CORNER, ELIMINATE SPLICES IN CONTROL WIRING (WIRE NUTS) UNDER FAN COIL. WANT TO SEE SHT. ROCK ABOVE ALL FAN COILS, PROPERLY SEALED. |