Permit: T03CM04894

Parcel: 11611005K

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM04894

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/1)CORRECTIONS MADE OK. OK TO COVER ALL AREAS
10/25/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)STAND PIPE RECEPTORS TO BE ROUGHED IN NO LESS THAN 6" AFF NOR MORE THAN 18" AFF. A TRAP ARM TO BE AT LEAST 2X THE TRAP ARM SIZE. A STAND PIPE RECEPTOR MUST BE BETWEEN 18"-30"
10/14/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)NOT READY FOR INSPECTION 2)WHERE ARE THE FULL SIZE CLEAN-OUTS IN BATHROOMS?
10/11/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)SUPPORT ALL HORIZONTAL OVERHEAD PIPING. BRASS OR S.S. SCREWS ON CLOSET FLANGES. 3" CLEAN-OUT REQUIRE 18" CLEARANCE. TRAP ARMS EXCEEDING 90 DEGREES WILL REQUIRE AN ADDITIONAL CLEAN-OUT 2)ROOF DRAINS OK WATER TEST OK
09/20/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CANNOT WET VENT 2" TRAP ARM INTO A 2" VENT FOR AUTO WASHER 2) RETEST SYSTEM