Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04894
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/13/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ALL UNITS WITH CORRECT UNIT NUMBERS INCLUDING DESIGNATION OF HOUSE METER MUST BE ON PERMIT & REQUESTS FORMS .OK TO CLEAR ALL METERS BLD #1 PER DAN AND STEVE LONG CONVERSTATION ON 1-13-05 | |
| 01/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/1)METER DESIGNATED ADDRESSES FOR EACH METER MUST BE INCLUDED ON PERMIT & REQUEST FORMS 2)CONDUCTOR SIZE TO SMALL FOR AC COMPRESSORS |