Permit: T03CM04894

Parcel: 11611005K

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM04894

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2004 FRAMING Approved IVRS - Inspection :*
10/28/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) EXCLUDES FIREWALLS
10/27/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) 2ND FLOOR CEILING
10/25/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) PLASTIC ICE MACHINE BOXES IN KITCHEN ARE NOT RATED FOR 1 HOUR WALLS. REPLACE WITH 22 GAUGE STEEL 2) PROVIDE LISTED SYSTEM FOR WASHER BOXES 3) EXCESSIVE WOOD REMOVED FROM STUD AT 2 X 6 BEARING PLUMBING WALLS 4) I DO NOT BELIEVE FLEX DUCT FOR BATH EXHAUST FANS IS LISTED FOR 1 HOUR
10/19/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
07/22/2004 FRAMING Not ready for Inspection IVRS - Inspection :*