Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04884
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/16/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) PLEASE PROVIDE A LETTER FOR LIABILITY SEAL OF PACKING AND ? | |
05/20/2004 | ELECTRIC - FINAL | Partial Approval | 1) SEAL HAVE BEEN FILL WITHOUT INSPECTION AS REQUESTED IN #1 OF PREVIOUS INSPECTION 2) FLOATS LABEL STATES 120/240V-PLEASE VERIFY CLASSIFIED LOCATION LABEL 3) MAINTAIN CLEARANCES ? SERVICE 4) CONTROLLER AND SWITCH DISCONNECT TO BE AS PER 430.102 A&B, 430.109 5) FINISH ITEMS #5 OF PREVIOUS INSPECTION 6) REVISE CONTROL PANEL DIAGRAM 7) OBSERVED 4 UNIONS AND 2 COUPLINGS IN 4 LOCATIONS OF UNDER GROUND RUN-ALL ARE MADE UP TIGHT | |
05/13/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO POWER UNTIL SEALS ARE INSPECTED. PACK EVERY OTHER AND CHICO EVERY OTHER. 2) CONDUITS TO HAZARDOUS LOCATION COVERED WITHOUT INSP. PLEASE UNCOVER FOR INSP. 3) JUNCTION BOXES HAVE WTR IN BOX. - DRY OUT. 4) VERIFY PUMPS LISTING AND LABELING FOR HAZARDOUS LOCATION. 5) PLANS CALL FOR A 30 AMP CIRCUIT - WE HAVE ONLY A 20 AMP PANEL SCHEDULE DOES NOT MATCH CIRCUIT DIRECTORY. 6) WHERE IS ELECTRIC FLOOR PLAN. |