Permit: T03CM04884

Parcel: 133231610


Addresses:

7150 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM04884

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) PLEASE PROVIDE A LETTER FOR LIABILITY SEAL OF PACKING AND ?
05/20/2004 ELECTRIC - FINAL Partial Approval 1) SEAL HAVE BEEN FILL WITHOUT INSPECTION AS REQUESTED IN #1 OF PREVIOUS INSPECTION 2) FLOATS LABEL STATES 120/240V-PLEASE VERIFY CLASSIFIED LOCATION LABEL 3) MAINTAIN CLEARANCES ? SERVICE 4) CONTROLLER AND SWITCH DISCONNECT TO BE AS PER 430.102 A&B, 430.109 5) FINISH ITEMS #5 OF PREVIOUS INSPECTION 6) REVISE CONTROL PANEL DIAGRAM 7) OBSERVED 4 UNIONS AND 2 COUPLINGS IN 4 LOCATIONS OF UNDER GROUND RUN-ALL ARE MADE UP TIGHT
05/13/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO POWER UNTIL SEALS ARE INSPECTED. PACK EVERY OTHER AND CHICO EVERY OTHER. 2) CONDUITS TO HAZARDOUS LOCATION COVERED WITHOUT INSP. PLEASE UNCOVER FOR INSP. 3) JUNCTION BOXES HAVE WTR IN BOX. - DRY OUT. 4) VERIFY PUMPS LISTING AND LABELING FOR HAZARDOUS LOCATION. 5) PLANS CALL FOR A 30 AMP CIRCUIT - WE HAVE ONLY A 20 AMP PANEL SCHEDULE DOES NOT MATCH CIRCUIT DIRECTORY. 6) WHERE IS ELECTRIC FLOOR PLAN.