Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/22/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/18/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC PANEL REQUIRES NON WATER BOND LABEL 2) A/C CONDENSOR DISCONNECT REQUIRES A 30" X 30" UNOBSTRUCTED WORK AREA 3) 18" DIAMETER HOLE IN EXTERIOR WALL REQUIRES STUCCO 4) FLEX CONDUIT AT A/C MUST BE SECURED TO WALL WITHIN 12" OF DISCONNECT 5) MAXIMUM ALLOWED CIRCUIT BREAKER FOR A/C CONDENSOR 40 AMP OVERFUSED 6) ABS PLASTIC ON ROOF REQUIRES PAINT UV PROTECTION 7) STOPPED INSPECTION TOO MANY ITEMS. HAVE HOUSE COMPLETED PRIOR TO NEXT INSPECTION |