Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04873
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
11/14/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
11/12/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
10/29/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PERMANENT LABELS ARE NEEDED ON DISCONNECTS 2) BOND BUSHING ARE NEEDED AT CONCENTRICS OVER 250V 250.97 3) WE HAVE MULTIPLE TERMINATIONS AT GROUND LUG 110.14 4) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 5) PLEASE CLEAN SURFACE UNDER LUG 250.12 6) DISCONNECT NOT FOR USE AS A RACEWAY 7) WHERE IS GFCI RECEPTACLE FROM PLANS 8) PLEASE SCHEDULE ELECTRICIAN TO OPEN LIVE 480V GUTTER FOR INSPECTION |