Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/22/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE. |
| 01/15/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT TO CONDENSORS. CONDUCTORS NOT SIZED TO AMPACITY OF UNITS. INSULATION THICKNESS ON REFER LINES DOES NOT MEET PLANS OR ENERGY CONSERVATION CODE. MUST BE MIN. 1" THICK. PROVIDE MIN. 3' CLEARANCE IN FRONT OF ELEC DISCONNECTS. PROVIDE FUSES IN DISCONNECTS FOR FAN COILS. |