Permit: T03CM04872

Parcel: 11449042N

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/22/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE.
01/15/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ #10 WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT TO CONDENSORS. CONDUCTORS NOT SIZED TO AMPACITY OF UNITS. INSULATION THICKNESS ON REFER LINES DOES NOT MEET PLANS OR ENERGY CONSERVATION CODE. MUST BE MIN. 1" THICK. PROVIDE MIN. 3' CLEARANCE IN FRONT OF ELEC DISCONNECTS. PROVIDE FUSES IN DISCONNECTS FOR FAN COILS.