Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Approved |
SENT TO TEP ON 02/10/04AM |
| 01/28/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) REMOVE BOND JUMPER AT SUB-PANEL |
| 01/27/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED BY TIM |
| 01/26/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) UFER SYSTEM NOT TIED TO NEUTRAL 2) TIE UFER AT DISCONNECT 250.24 99 NEC |
| 01/22/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ 1) FINISH ITEM #1, 2, 3 AND 7 OF FIRST INSPECTION 2) MOVED DISCONNECTS NOW NEED TO BE LABELED 3) WHERE IS PERMANENT ADDRESS LABEL 4) A REFEE HAS BEEN ACCESSED PER ADMINISTRATIVE CODE |
| 01/15/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SUPPORT CONDUITS AS PER CODE 2) WE HAVE MULTIPOLE TERMINATIONS AT DISCONNECT LUGS 3) TIGHTEN LOOSE FITTINGS 4) LABEL BREAKERS 5) PLEASE PROVIDE REJECTION PINS AT SERVICE 6) PROPERLY INSTALL LOCK NUTS AT SERVICE 7) MAINTAIN WORKING CLEARANCE AT A/C DISCONNECTS 8) FINISH ITEMS #1, 2, 3, 6, 7 AND 8 OF INSPECTION DATED 12/18/03 |
| 12/18/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |