Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
12/19/2003 ELECTRIC - UFER Approved IVRS - Inspection 0000*
12/18/2003 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE VERIFY LISTING FOR RED PVC TO TEP TRANSFORMER 2) BONDING DEVICES NEEDED ON ALL POINT AT SERVICE NIPPLES AND RISER 250.94 3) VERIFY USE OF BY PASS METER WITH POWER COMPANY TEP 4) FINISH CONNECTION OF CONDUCTORS 5) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 6) BOND DISCONNECT ENCLOSURE 7) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 250.24 8) UNCOVER GROUNDING ELECTRODE SYSTEM 9) FINISH ELECTRIC INSTALLATION 10) WHERE IS CITY APPROVED PLANS ?