Permit: T03CM04862

Parcel: 113080100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/03/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/26/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PLEASE REVISE " ELECTRIC SERVICE" DIAGRAM TO REFLECT THE ELIMINATION OF SERVICE DISCONNECT/SWITCH #3 2) THE FEEDER CONDUCTORS TO PANEL "SAB" ARE NOT SIZED PER PLAN. CHANGE OUT OR HAVE ENGINEER OF RECORD REVISE ON PLAN 3) PLAN SHOWS TWO 70 AMP SUB-BREAKERS IN PANEL "SAB"-PLEASE CHANGE FOLLOWING ENGINEERS PLAN OR REVISION 4) "EBO" WALL-PAK IS NOT OPERABLE