Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM04861
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ CORRECTIONS OK. | |
| 01/23/2004 | MECHANICAL - FINAL | Partial Approval | ACCESS PANELS IN HARD DUCT, NEAR FIRE DAMPERS, SUGG 10" SQ. LARGE hard duct. provide break away joints AT FIRE DAMPER SLEEVE. SEAL ALL OPENINGS IN RATED WALL. |