Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/14/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/ 1) OK POLE LIGHT U.G. PARKING LOT SIGN 2) COMPLETE SERVICE MAKE-UP, PROVIDE LETTER OF TORQUE | |
| 07/01/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/ 1) OK DINING ROOM #4 AND 3 2) OK PULL BOX FOR SECONDARYS | |
| 06/11/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/ 1) OK UNDERGROUND SECONDARYS FROM SES TO S.W. CORNER, CALL WHEN PULL BOX INSTALLED, OK SECONDARYS FROM X-FORMER TO 100' SOUTH | |
| 04/27/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: OK UNDER SLAB FEEDERS, BRANCH CIRCUITS, COMM, DATA, OK ELECTRIC ROOM U.G. |