Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 01/14/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NOTES: 1) COMPLETE MAKE-UP IN J-BOXES, SUPPORT J-BOXES TIE UP FLEX OR FIXTURE WHIPS LAYING ON GRID. 2) SUPPORT EMT CONDUIT WITHIN 3' OF J-BOXES. FLEX WITHIN 12". CONTRACTOR RESPONSIBLE TO SUPPORT EXISTING J-BOXES AND CONDUIT USED TO TIE-IN NEW OR RELOCATED EQUIPMENT FOR THIS PROJECT. 3) OK CONDUIT SUPPORTS ABOVE RELOCATED PANEL. |