Permit: T03CM04852

Parcel: 137279900

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM04852

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - ABOVE CEILING Approved
01/14/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ NOTES: 1) COMPLETE MAKE-UP IN J-BOXES, SUPPORT J-BOXES TIE UP FLEX OR FIXTURE WHIPS LAYING ON GRID. 2) SUPPORT EMT CONDUIT WITHIN 3' OF J-BOXES. FLEX WITHIN 12". CONTRACTOR RESPONSIBLE TO SUPPORT EXISTING J-BOXES AND CONDUIT USED TO TIE-IN NEW OR RELOCATED EQUIPMENT FOR THIS PROJECT. 3) OK CONDUIT SUPPORTS ABOVE RELOCATED PANEL.