Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM04848
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2003 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) ON FINAL PROVIDE CONDENSATE DRAIN LINE FOR A/C UNITS. DISCHARGE INTO AN APPROVED LOCATION. PROVIDE OUTSIDE AIR INTAKES. SECURE ELECTRIC CONDUITS AND DISCONNECTS. COVER CANVAS CONNECTOR EXPOSED TO SUNLIGHT. USE SUN RESISTANT T-STAT WIRE OR USE CONDUIT. REPLACE ALL MISSING ACCESS PANELS AND GUARDS ON A/C EQUIPMENT |