Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T03CM04848
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2003 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
11/13/2003 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1) ELEC WHIPS, DATA CABLES, ETC SHOULD NOT BE SUPPORTED BY GRID. 2) FLEX DUCT IN RESTROOM TO BE SUPPORTED EVERY 4' ( NO KINKS). 3) ANY GRID WIRES MORE THAN 1/6 OUT OF VERTICAL REQUIRE OPPOSING WIRE. 4) OK TO PLACE TILE 2 MAIN ROOMS. |