Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/17/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO POST BOND FOR POWER 2. BOND CLAMP TO WATER TO BE ACCESSIBLE & LISTED FOR EARTH CONTACT 3. GROUND RODS TO BE MINIMUM 6' APART -- 250 4. BOND TO CT CAN UNDERSIZED - 250.66 5. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - 250.6 6. IDENTIFY SERVICE DISCONNECTS - NEC 230.72 B 7. GROUNDING ELECTRODE CONDUCTOR FOR TRANSFORMER NOT TO RUN THROUGH OTHER RACEWAYS OR EQUIPMENT UNLESS MADE ELECTRICALLY CONTINUOUS - NEC 250.64E 8. PROPERLY IDENTIFY SERVICE/EQUIPMENT NEUTRALS - NEC 200 9. BOND RACEWAY PER NEC 250.97 10. INSTALL FUSES 11. NEUTRAL NOT TO MAKE LOAD SIDE CONNECTION TO GROUND - NEC 250 (IN HOUSE PANEL) 12. HOUSE PANEL NEEDS MAIN BREAKER AND HOLDDOWN KIT |
|
| 10/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EXTERIOR EAST SIDE SOFFIT CANS (7) COVER |