Permit: T03CM04823

Parcel: 10701040A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/17/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO POST BOND FOR POWER
2. BOND CLAMP TO WATER TO BE ACCESSIBLE & LISTED FOR EARTH CONTACT
3. GROUND RODS TO BE MINIMUM 6' APART -- 250
4. BOND TO CT CAN UNDERSIZED - 250.66
5. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - 250.6
6. IDENTIFY SERVICE DISCONNECTS - NEC 230.72 B
7. GROUNDING ELECTRODE CONDUCTOR FOR TRANSFORMER NOT TO RUN THROUGH OTHER RACEWAYS OR EQUIPMENT UNLESS MADE ELECTRICALLY CONTINUOUS - NEC 250.64E
8. PROPERLY IDENTIFY SERVICE/EQUIPMENT NEUTRALS -
NEC 200
9. BOND RACEWAY PER NEC 250.97
10. INSTALL FUSES
11. NEUTRAL NOT TO MAKE LOAD SIDE CONNECTION TO GROUND - NEC 250 (IN HOUSE PANEL)
12. HOUSE PANEL NEEDS MAIN BREAKER AND HOLDDOWN KIT
10/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EXTERIOR EAST SIDE SOFFIT CANS (7) COVER