Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/28/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) TRANSFORMER [225 KVA] TO HAVE 2/0 COPPER CONDUCTOR TO GROUND WATER LINE. 2) COMPRESSOR OVERFUSED - 150 AMP FUSES TO BE BROUGHT DOWN TO PROTECT #4 COPPER FEEDERS. |