Permit: T03CM04795

Parcel: 12909010A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/30/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/28/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) TRANSFORMER [225 KVA] TO HAVE 2/0 COPPER CONDUCTOR TO GROUND WATER LINE. 2) COMPRESSOR OVERFUSED - 150 AMP FUSES TO BE BROUGHT DOWN TO PROTECT #4 COPPER FEEDERS.