Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM04789
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2004 | FRAMING | Approved | IVRS - Inspection 0000* | |
11/25/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
11/21/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO DRYWALL-CHECK FOR SUPPORTING CRIPPLE STUD IN MIDDLE BEDROOM RETURN AIR SUPOPORTING PLATE SPLICE AT FINAL INSPECTION | |
11/20/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) WALL TOP PLATE BREAKS (SPLICES) MUST OCCUR OVER BEARING MEMBER | |
11/19/2003 | FRAMING | Denied | IVRS - Inspection 0950*/ 1) SEAL ALL PENETRATIONS 2) LATH NOT COMPLETE 3) GROUND ALL METAL ELETRIC BOXES PROPERLY 4) SHEAR PANELS IN TRUSSES NOT PROPERLY NAILED 14/DT1 5) BOND GAS LINE 6) RECESSED LIGHT REQUIRES 1/2" COMBUSTIBLE 7) HEADER MUST BEAR ON TRIMMERS 8) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSSES AND NON-BEARING WALL 9) W/C REQUIRES 15" CLEARANCE TO TUB 10) STOPPED INSPECTION, TOO MANY ITEMS |