Permit: T03CM04777

Parcel: 11931022Q

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM04777

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2005 FRAMING Approved IVRS - Inspection :*
01/03/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HTT16 HOLD DOWNS REQUIRE 5/8" BOLTS
2) MASTER CLOSET MISSING SW3 OSB
3) 4 X 6 POSTS MISSING MASTER BEDROOM
4) HOLDOWN OUT OF WALL 2ND AND NOT BEARING ON FOUNDATION SW5
5) NAIL PROTECT ALL WIRES AND WITHIN 1 1/4" OF STUD SURFACE
6) NAIL POST BASE BY ENTRY
7) KITCHEN SHEARWALL #3 REQUIRES OSB
8) DINING ROOM SW3 OSB MUST EXTEND TO TOP PLATES. ALSO SW5 AND HALL
9) NAIL SW3 TO LADDER BACK AT TOP
10) POST BASE MISSING READING ROOM AND CAPS AT ALL SPLICES
11) FIREBLOCK 6" CHASE GARAGE
12) SHIM POSTS IN 8 SIDED TOWER ALL HEADERS
13) SMOKE DETECTOR REQUIRED LOFT
14) SMOKE DETECTORS CANNOT BE WITHIN 36" OF AIR REGISTER AND MUST BE 12" OF CEILING
15) NAIL PROTECT RANGE DUCT
12/23/2004 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) M/BR SHEARWALL 3 MISSING OSB AND ANCHOR BOLTS
2) M/BR CLOSET SHEARWALL 1. REMOVE-NOT NEEDED NAIL PROTECTION
3) M/BR ? SHEARWALL 5. HOLDOWN MISSING/OSB MISSING AND ANCHOR BOLTS MISSING. ALSO HOLDOWN BOLT OUT OF WALL AND WALL NOT BEARING ON FOUNDATION PROVIDE ENGINEER APPROVED REPAIR
4) LAUNDRY SHEARWALL 1 MISSING BLOCKING AT TOP OF WALL AND REQUIRES SHEAR TO JOINTS
5) POST BASES MISSING 2 POSTS BY ENTRY
6) KITCHEN DBL SHEARWALL 1 RWQUIRE AB'S AT 32" ON CENTER
7) ENTRY SHEARWALL 3 MISSING DBL STUDS AND OSB
8) KITCHEN SHEARWALL 3 MISSING OSB AND SHEAR TO JOISTS
9) FAMILY MISSING SHEARWALL 5 AND ANCHOR BOLTS
10) FAMILY ROOM S/W 3 MISSING OSB AND STUDS AND AB OVER BORED. USE 1/4" THICK X 3" WASHERS ON ALL OVER BORDED PLATES
11) ALL SHEARWALLS REQUIRE DOWN STUDS AT ENDS
12) STUDY SHEARWALL 3 MISSING LADDER BACK AT 24" ON CENTER
13) SHEARWALLS MUST BE FRAMED AT 16" ON CENTER
14) READING ROOM MISSING SHEARWALL 5 AT SWITCH AND AT DOOR WAY
15) CHECK ALL OF HOUSE FORE SHEARWALL CONSTRUCTION
16) STOPPED INSPECTION, TOO MANY ITEMS
11/23/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) CANNOT APPROVE THE FRAME UNTIL ALL TRADES ARE APPROVED