Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/02/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 11/17/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) HANGING NAILS AT GARAGE LEDGER USE 16D'S NOT 8D'S 2) INSTALL X BRACING ON FRONT OF HOUSE, AT MAIN TRUSSES 3) OK TO DRY IN, DON'T LOAD ROOF |
| 11/14/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NAIL OFF ROOF AT GARAGE HIP 2) OSB TURNED WRONG WAY 5 PIECES 3) SHEAR WALLS HOLES REPAIRED, BLOCKED, NAIL OSB TO BLOCKS |
| 11/10/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |