Inspection Status: Approved
Inspection History: ROOF NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/26/2003 |
ROOF NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 11/24/2003 |
ROOF NAILING |
|
Denied |
IVRS - Inspection 0999*/ 1) MANY AREAS OF OSB ROOF PANELS LOOSE-NOT NAILED 2) OSB ROOF PANELS REQUIRE 1/8" END AND EDGE CLEARANCE 3) OSB PANELS MUST BE INSTALLED WITH GRAIN PERPENDICULLAR TO TRUSSES 4) SHIM 3 PT BEARING TRUSSES TO PROVIDE 12' X 3 1/2 BEARING AT INTERIOR WALL |