Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
01/27/2004 SHEET ROCK NAILING Approved IVRS - Inspection 0000*
01/16/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0935*/ 1) ALL REPEAT ITEMS. REFEE 2) THE MINIMUM ALLOWED LENGTH OF DRYWALL SHEAR PANELS IS 96" PER IRC SECTION 602.10.4 3) DRYWALL SHEAR PANELS LESS THAN 9 FEEET IN LENGTH MUST BE INSTALLED VERTICALLY IRC TABLE 602.3 (1) NOTE D 4) #5 SHEAR WALL REQUIRES ALL EDGES BLOCKED PLAN 5) MAXIMUM ALLOWED GAPS IN DRYWALL SHEAR WALLS IS 1/4" GA.216.2000 4.6.5 6) FILLING OF GAPS IN DRYWALL BY THE USE OF SCRAP STRIPS NOT ALLOWED GA.216.2000-4.6.5.2 6) MAXIMUM ALLOWED GAPS AT DRYWALL PENETRATIONS 1/8" 7) NAILING OF DRYWALL WITHIN 3/8" OF EDGE NOT ALLOWED GA.216.2000-4.8.2
01/12/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0935*/ 1) NO CHANGE FROM 1/9/04. REFEE
01/09/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0999* DENIED. HOUSE DRY WALL DOES NOT APPEAR TO BE PROPERLY INSTALLED. PROVIDE GYPSUM WALLBOARD INSTALLATION STANDARD OR COMPLY WITH GYPSUM ASSOCIATION, APPLICATION AND FINISHING OF GYPSUM BOARD SPECIFICATION GA -216-2000. 2) BLOCK ALL REQUIRED ESGES AS SPECIFIED ON PLAN. 3) 4X 8 SHEATS OF DRYWALL MUST BE INSTALLED VERICALLY IRG TABLE R602.3L (1) NOTE D. 4) MINIMUN LENGH OF GYPSUM BOARD SHALL BE 96 INCHES. IRC 602.104. NEXT FAILURE WILL BE CHARGED AT REINSPECTION FEE.
01/08/2004 SHEET ROCK NAILING Denied IVRS - Inspection 0999*/ 1) FILL ALL GAPS LARGER THAN 1/8" 2) PROVIDE DRYWALL CLIPS AT ALL NON SUPPORTED EDGES