Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/30/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/26/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* NO PLANS ON SITE |
| 12/23/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 12/15/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) WATER HEATER PLATFORM 2 X 4 CUT 2) NO TEST ON WATER LINES OR DWV'S 3) COMPLY WITH TABLE E 3702.1 2000 IRC ROMEX NOT ALLOED TO BE STAPLED ON IT'S SIDE 4) ROMEX NEXT TO FRIDGE LINE IN CIELING INSULATION BORKEN 5) FIREPLACE NOT INSTALLED 6) STOPPED INSPECTION. RECALL WHEN READY. SEE PREVIOUS INSPECTIONS DATED 12/08/03 AND 12/04/03. NEXT FAILURE WILL RESULT IN A REFEE |
| 12/08/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HOLDOWNS MISSING THRU-OUT 2) HEADERS MISSING BETWEEN DINING AND LIVING ROOM AND AT RIBBON BY STAIRS 3) BEARING STUD MISSING AT FRONT BATH BY 3" AB'S BENT 4) PLUMBING NOT COMPLETE (UPSTAIRS) 5) W/H VENT LOOSE CHECK UPSTAIRS 6) FIREPLACE NOT IN PLACE 7) REJECTED-HAVE TRADES CHECK PRIOR TO REINSPECTION |