Permit: T03CM04684

Parcel: 125122640


Addresses:

3444 E 4TH ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/04/2004 FRAMING Approved IVRS - Inspection :*
09/30/2004 FRAMING Cancelled PER CALL FROM W. BERRING
09/27/2004 FRAMING Cancelled CANCELLED PER PAPERWORK TURNED IN BY B. STEVENS
09/24/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) FRAMING AT MASTER BED/BATH OK TO COVER 2) MASTER BED/BATH OK TO SHEET ROCK
09/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PROVIDE UL LISTING FOR INSTALLED GROUND CONNECTORS 2) PROVIDE GROUND PIG TAILS FOR EACH SWITCH AND OUTLET 3) PROVIDE OUTLET WITHIN 6' OF DOOR AT EASTSIDE OF ENTRY 4) WIRING NOT COMPLETE 5) MANY WALLS NOT LOCATED PER PLAN 6) JUNCTION BOXES MUST BE ACCESSIBLE AFTER DRYWALL 7) MASTER BATH NOT PER PLAN 8) CANNOT INSPECT FRAME UNTIL ALL PLUMBING, ELECTRIC ARE COMPLETE 9) STOPPED INSPECTION, NOT COMPLETE ENOUGH TO BE INSPECTED
06/15/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) PARTIAL ON FRAMING PENDING PLB/ELECT INT.