Permit: T03CM04683

Parcel: 122030730

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ CONFIRMED PROPER FUSING, WIRE SIZE FOR A/C EQUIPMENT. OK FOR FINAL C OF O.
03/11/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ PERMANENTLY MARK UNIT DATA PLATES WITH PROPER HT STRIP INSTALLED AND FUSE DISCONNECT ACCORDINGLY. #8 WIRE NOT ADEQUATE WITH 60 AMP FUSES. TIGHTEN SEAL TITE FITTINGS. DO NOT USE A CHASE NIPPLE TO CONNECT FROM DISCONNECT TO SERVICE OUTLETS ON ROOF.