Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CONFIRMED PROPER FUSING, WIRE SIZE FOR A/C EQUIPMENT. OK FOR FINAL C OF O. |
| 03/11/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PERMANENTLY MARK UNIT DATA PLATES WITH PROPER HT STRIP INSTALLED AND FUSE DISCONNECT ACCORDINGLY. #8 WIRE NOT ADEQUATE WITH 60 AMP FUSES. TIGHTEN SEAL TITE FITTINGS. DO NOT USE A CHASE NIPPLE TO CONNECT FROM DISCONNECT TO SERVICE OUTLETS ON ROOF. |