Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM04675

Parcel: 138133450

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/23/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
01/21/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NO ADDRESS 2) WHITE WIRES CANNOT BE HOT IN PANEL AND AT UNITS 3) ANCHOR A/C WHIP 4) MARK ATTIC A/C LABEL TO INIDICATE PROPER AMPACITY, LABEL INDICATE FA4B WITH HEAT STRIP MINIMUM 31.4/33.8 VA WIRED WITH 12 GUAGE WIRE 5) IMPROPER DISCONNECT WIRE COLOR CODE 6) A/C CONDENSATE NOT CONNECTED 7) A/C WHIP BLOCKS ACCESS TO ATTIC 8) A/C WHIP NOT SECURE 9) NO ELECTRIC PLAN ON SITE