Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 11/17/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection :* |
| 11/06/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
#8 REBAR IN AN 8" CELL REQUIRES A LAP SPLICE OF 68" IN LENGHT WHEN YOU USE 1800 PSI GROUT. YOU DO NOT HAVE THE REQUIRED LAP LENGHT COMING OUT OF SLAB OR ABOVE GROUT LIFT. |