Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM04639
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/19/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) WIRES NOT CONNECTED TO FAN COIL PROPERLY (BROKEN FITTING) 2) SECONDARY DRAIN PIPE HAS BACKPITCH. USE A CLAMP TO SECURE DRAIN. 3) DO NOT REDUCE PRIMARY DRAIN CONNECTION TO LAV. |
|
| 05/17/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE SECONDARY DRAINS ON FAN COILS. TERMINATE IN A CONSPICUOUS LOCATION. 2) PROVIDE A 3/4" I.D. HOSE AND FITTINGS WHERE CONDENSATE DRAIN CONNECTS TO LAV. TAILPIECE. OK FOR TEMP POWER. |