Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK FINAL |
| 06/08/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ OK TEMP C OF O. |
| 06/07/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) KITCHEN OUTLETS TO BE GRID PROTECTED. 2) BREAKER AMPACITY FOR CENTERLINE 8 NM CABLE TO BE AS PER 336-26. |
| 06/01/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ CANCELLED BY CONTRACTOR. |
| 05/26/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK UNITS 113, 114, 115, 116, 213, 214, 215, 216, 312, 314, 315 AND 316 TO CLEAR |
| 05/17/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) LIGHTING ON OUTDOOR WALL TO MEET CITY LIGHTING ORDINANCE REQUIREMENTS SECTION 5. LIGHT IS A 150 W HPS. 2) BOXES MORE THAN ΒΌ" FROM BOX TO SURFACE IN NON-COMBUSTABLE TO HAVE APPROVED EXTENDER RINGS - METAL NOT APPROVED 370-20. 3) BREAKERS HAVE BEEN PAINTED OVER MAKING IT UNABLE TO READ OVER CURRENT RATINGS - EXCESSIVE PAINT ON TERMINALS, ALSO LABELED, 110-12, 110-22. 4) PLEASE INSTALL HOOD. 5) CONDUIT ON OUTSIDE OF BLDG TO BE REMOVED BACK TO 1ST JUNCTION BOX AND SEALED. / LEFT PAPERWORK FOR TEMP POWER FOR TEST. |