Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM04639
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ OK ROUGH ELECTRIC. | |
| 04/01/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ROUGH 1ST AND 2ND FLOOR 2) OK 314 ROUGH 3) 315 AND 316 WE HAVE OVER CONDUCTOR FULL AND HALL WAY CEILING | |
| 03/30/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0935*/ 1) NM CABLE TO BE SUPPORTED WITHIN 1`2" OF CANS AND FANS AND BOXES AND NEW CABLES AT PANELS 2) COMPLETE #10 OF PREVIOUS INSPECTION 3) A REFEE AS PER ADMINISTRATIVE CODE HAS BEEN ASSESSED | |
| 03/26/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK EXTERIOR WALLS-NOT HALLWAYS | |
| 03/15/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) RESUPPORT AND SUPPORT NM CABLE WITHIN 12" OF BOXES. ALSO SE CABLES. 2) APPROVED CONNECTORS ARE NEEDE AT EXHAUST FANS. 3) FILL UNUSED OPENINGS AT PANEL. 4) BOXES/FANS TO HAVE 6" OF CONDUCTORS AT BOX. 5) REPLACE DAMAGED RECESSED CAN. 6) RE-INSERT CABLES INTO BOXES. 7) TIGHTEN LOOSE FITTINGS. 8) BOXES NOT ATTACHED TO STRUCTURE. 9) USE APPROVED METHODS FOR TERMINATION OF NEUTRAL. 10) WE HAVE CONDUCTOR OVERFILL AT BOXES. 11) PLEASE VERIFY L-11 LICENSE FOR ELEC. CONTRACTOR. | |
| 01/30/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) REPLACE BROKEN BOX IN FIRE WALL 2) PROTECT CABLES AT STUDS 3) RE-INSTALL EXHAUST FANS, LIGHTS BOXES 4) RE-INSPECT CABLE SHEATHING BACK INTO BOXES 5) FINISH HALLWAY 6) PROTECT PVC CONDUITS AT STUDS |