Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM04602

Parcel: 141173930

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM04602

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*/ 1) NOTE: WILL CHECK AT INTERMEDIATE INSPECTION. ADD SPACER DOUBLE TOP PLATE TO BOTTOM OF SHEAR PANEL, NAIL TO TOP PLATE WITH 16D'S 12" ON CENTER. SHEAR PANELS TO BE 48" ON CENTER START AT EITHER SIDE OF PA'S