Permit: T03CM04598

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/24/2003 PLUMBING - FINAL Approved 1) PLAN CALLS FOR FUNNEL DRAIN AT COFFEE MACHINE. A STAND PIPE RECEPTOR WITH A BELL REDUCER IS NOT AN APPROVED INDIRECT WASTE RECEPTOR. BESIDES WITH THE DRAINS EXTENDING SEVERAL INCHES INSIDE THE STAND PIPE CAN ALLOW MIGRATION OF SEWAGE INTO EQUIPMENT. 2) RE-INSPECTED 2:30 PM - CORRECTIONS MADE OK - OK FOR C OF O PANDING ANY OTHER INSPECTIONS.
12/22/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE THRU A WYE BRANCH FITTING OR EQUIVELANT SWEEP 2) A TRAP ARM MAY ONLY CHANGE DIRECTION 90 DEGREE WITHOUT THE USE OF ALL ADDITIONAL CLEANOUT 3) PROVIDE CERTIFICATE OF INSPECTION FOR RP DEVICE
12/22/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ EACH PIECE OF WTR SUPPLIED EQUIPMENT I.E. COFFEE MAKERS, TEA BREWERS ETC. REQUIRE THEIR OWN BACKFLOW DEVICE.