Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ OK FINAL. |
| 05/04/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) BATHROOM SWITCH AND LIGHT IN OFFICE TO BE WIRED AS PER CODES. OPEN CONDUCTORS TO BE INSTALLED IN A RACEWAY SYSTEM OR OTHER APPROVED WIRING METHOD 2) FINISH #3 OF PREVIOUS INSPECTION FOR TANSFORMER DIMMING |
| 03/17/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ ITEMS 6 AND 7 DATED 12/9/03 OK. FINISH PREVIOUS ITEMS - OFFICES STILL LOCKED. |
| 03/15/2004 |
ELECTRIC - FINAL |
|
Cancelled |
IVRS - Ri canceled |
| 03/09/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ ROOF OK. DRESSING ROOM OK. BAR OK. / 1) CLEAN FLOOR IN FRONT OF SERVICE EQUIPMENT. 2) OFFICE STILL LOCKED. 3) FINISH ITEMS 2,3,6,7, OF PREVIOUS INSP. |
| 12/09/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ROOF: TAKE CARE OF LV TRANSFORMERS AND WIRING NOT LISTED FOR LOCATION BLDG: 1) GUTTER COVER TO BE OF SAME THICKNESS AS GUTTER 2) REROUTE DRAIN FROM IN FRONT OF SERVICE EQUIPMENT 3) NEON TRANSFORMER TO BE SWITCHED NOT DIMMED-VERIFY DIMMING OF TRANSFORMER-INSTALL GTO CABLES AS PER CODE 4) DISHWASHER RECEPTACLE TO BE WATER PROOF 5) OPEN WALLS AT LAST AS MARKED ON PLANS 6) USE OF MULTI TAPS AND EXTENSION CORDS NOT ALLOWED FOR WIRING METHODS 7) FILL ALL UN-USED OPENINGS 8) PROPERLY WIRE PLUG MOLD IN DRESSING ROOM 9) REPAIR OR CORRECT ITEMS AT BAR 10) MEET WITH MIKE REED AND WALKED JOB. HE IS AWARE OF OTHER VIOLATIONS IN BLDG. WORK IS PROGRESSIVE. UPSTAIRS OFFICE OK, MANAGER EAST SIDE OK, STORAGE ROOM OK |
| 12/08/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/05/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CANCELLED PER JESSE. |
| 10/29/2003 |
ELECTRIC - FINAL |
|
Denied |
1) MET WITH JESSIE VESAR FROM MEHL ELECTRIC. PLEASE OPEN AREAS OF WALLS AS DISCUSSED-6 PLACES 2) WE WALKED BLDG AND ROOF AND FOUND VARIOUS LOCATIONS WITH CODE VIOLATIONS AND BUILDING SAFETY ISSUES. EX: OPEN CONDUCTORS, OPEN BOXES, OPEN CABINETS, IMPROPER INSTALLED NEON INSTALLATIONS AND VARIOUS OTHER ISSUES. PLEASE REPARI UNSAFE ELECTRICAL CONDITIONS AS DISCUSSED 3) I WILL FINISH BLDG INSPECTION ON NEXT CALL OUT DUE TO LIMITED TIME ( BLDG: PLANS NOT COMPLETE, READ PLUMBING INSPECTORS REPORT. NEED ROOF FRAMING PLAN FOR AREA SUPPORTING NEW A/C UNIT. NEED ARCHITECTURAL FLOOR PLANS SHOWING EXITS, CORRIDORS, AND ALL ROOMS EXIT SIGN EMERGENCY LITES ETC.) (PLUMBING: PLEASE PROVIDE A COMPLETE SET OF WORKING DRAWINGS WASTE VENTS AND WATER. ISOMETRIC DRAWINGS ARE REQUIRED BY PLAN CHECK. NEW GAS LINES HAVE BEEN INSTALLED ON ROOF AND THROUGHOUT THE BLDG. NEW EQUIPMENT ON ROOF AND NEW KITCHEN EQUIPMENT HAS BEEN INSTALLED AND COVERED WITHOUT INSPECTIONS SINKS, FLOOR DRAINS, DISHWASHING EQUIPMENT ETC. WILL REQUIRE A WORKING DRAWING FOR GAS LINES INSTALLED ON ROOF THORUGHOUT BLDG. PLEASE PROVIDE TOTAL LENGTH AND TOTAL BTU'S ON COMPLETE SYSTEM. A NEW FULL BATH HAS BEEN INSTALLED AND COVERED ON SOUTH SIDE OF BLDG REAR KITCHEN. RECORDS HAVE BEEN CHECKED FOR PERMITS AND PLANS. RECORDS DO NOT EXIST FOR THIS AREA. AFTER A WALK THROUGH OF THE BLDG NUMBERS OF CODE VIOLATIONS HAVE BEEN FOUND. REQUIRED BACK FLOW DEVICES MISSING FROM EQUIPMENT. INDIRECT WASTE LINES IN VIOLATION. WATER HEATER IN VIOLATION. GAS LINES AND DRAIN LINES BLOCKING ACCESS TO ELECTRICAL EQUIPMENT) |